The Vocia® enhanced Life Safety Interface 16e (LSI-16e) is a networked device that serves as an interface between a Vocia system and emergency or fire alarm systems. The LSI-16e may accept up to three sources of power: main power is from an external, standards compliant and battery backed 24V DC source; the LSI-16e can also utilize Power over Ethernet (PoE) delivered via either of its two network ports. The device is equipped with parallel I/O ports for direct interface to fire and emergency control equipment. The LSI-16e uses Ethernet-based control protocols to function within a Vocia system.
Parallel I/O ports for direct interface with fire alarm
and emergency equipment
8 monitored I/O and 8 control inputs
Redundant network connection and power supply options
Power and data over a single Ethernet cable
Local storage of configuration data
Rotary switches for unit identification
Up to 4 discrete emergency inputs
16 additional general purpose inputs can be
programmed to play an emergency message, enable
zone reset or zone silence; maximum of 10 inputs can
be assigned per emergency zone
Each general purpose input can be programmed as
TTL, high range or monitored high range
General purpose inputs allow monitoring for short to
ground and open circuit
Up to 500 virtual inputs via RS232 or Ethernet
Provides system health monitoring via RS232 or
Ethernet
Status LEDs
Rack mountable (1RU)
CE marked and RoHS compliant
EN 54-16 certification pending
Covered by Biamp Systems’ warranty
Spec Sheet available - Yes
Depth:
10 in
Height:
1.75 in
Width:
19 in
Product Weight:
6.40 lbs
Operating Temperature (Maximum):
113 F
Operating Temperature (Minimum):
32 F
System Fault Relay:
Type:
Single 'Form C' voltage-free SPST change-over contact
Load:
Resistive
Maximum Operating Voltage:
125VAC, 60VDC
Maximum Operating Current:
600mA AC, 1A DC
Maximum switching capacity:
37.5VA, 30W
Minimum permissible load:
10µA @ 10mVDC
Control Inputs:
Number:
Eight
Cathode presented at input - pull low to enable.:
Sink Current:
Min:
1mA
MAX:
6mA
Maximum Terminal Voltage:
24V
Isolation:
3kV
Monitored I/O:
Maximum Continuous Current:
0.35A
Current limit:
0.8A
Maximum External Supply:
35V
VMon Input Shutdown:
35V
General Purpose Inputs:
High Range Logic Low:
0-11V DC
High Range Logic High:
12-30V DC
High Range Hysteresis:
1V +/- 20%
TTL Logic Low:
0-0.8V
TTL Logic High:
2-5V
TTL Hysteresis:
1V +/- 20%
Input Transient Protection:
+/- 8KV peak
Input Isolation:
500V RMS (isolation from LSI-16)
RS232 port:
Baud Rate:
57600
Connection:
RJ45 with shielded Ethernet/PoE cable (Cat5, Cat5e, Cat6 or Cat7)
Power:
Main:
24V DC 15W
PoE:
802.3af Class 3
Compliance:
FCC Part 15B CE marked EN 54-16 certification pending RoHS Directive UL 60065 Listed, E215636 C-UL Listed, E215636 C-Tick, N24138 (Australia)